We have 800KW motor operating at 6600Volt,50 Hz
supply.During 1st startup it tripped on overcurrent
trip.It's FLA is 88 Amps.The K factor of Thermal overloaaad
was set on .94 initially.then we set at 0.97 and then it
started fine.i dont understand why it tripped first?What
are the protections which comes in picture during starting ?
Answer Posted / karthik_elec
u did'nt mention which type of starter you used,and which type of operation no load or full load, this type large motors always used soft starter only, auto transformer will not use, any way at the time of starting auto transformer only gradually increase the applied voltage , at that time the motor will take more amps to obtain the specific torque, due to that only, after obtain normal amps it will not take 88 amps also, because this is 100% efficiency current, below that only....
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Is a d.c.compound motor is use as a booster? how?
any idea abt REVERSE METERING concept.........?
What are the main parts of central chiller plant? Explain the function of each stage.
Why earthing is necessary for any equipment?
Initially, when the input is not equal to the output — what type of response is this?
What Is HO factor in power selection
What is meant by rotor?
what are the tests comes under the type test, what tests comes under routine tests.
why the neutral point in connnection oscillates?
In synchronous motor, how the field current is related to armature current..i know its inversely proportional..but concept wise...i was nt clear....pls help me...
what is the stear deltaprinceple?
what is mean by ideal infinite bus? why it is required to consider in fault short circuit calculations?
What is limitedly stable system?
electrical ques
What is the difference between PLC and Embeded system