After synchronization with grid how to maintain the
power factor in lagging or in leading? if lead of lag what
is the problem?
Answer Posted / k.prakashchandra
Pf lagging means over-excitation ,leading pf is caused by
under excitation.Maintain pf at 0.95 t0 0.98 lagging by
varying the excitation .
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is the automatic voltage regulator with servomotor?
What are the different power system losses and how can it be eliminated?
How will change the frequency in distribution side?
how balanced in star delta connection ?
What is the control action?
what is meaning of sympathetic tripping with respect to relays and give the values for current carrying capacities for copper and aluminium cables from 16sq mm to 500sq mm
what is v/f control in VFD?
how to select correct size of power cable for inverter duty motor
What is resolver and glass scale in CNC how they work?
How to calculate the phase to phase clearness of HT /// LT bus bar?????
What is the limitation of kirchoffs law?
In ht capacitor ckt we are using LBS Panel it having isolator with fuse, one of HT fuse flash over, so what is reason behind this event.
A 7 storey building has a floor area of 35,000sq.ft on each storey. On the ground floor 11KV electrical sub-station is to be erected. A load of 3kw for every 400sq.ft (p.f is 0.8) is proposed for each floor. fire pump 7.5hp, water pump 5hp, lift 2 nos, each 10hp and 20shop load of each shop is 5kw. calculate a. load each floor b. total load of building c. L.T feeders for aech floor and from transformer to main. d. distribution diagram e. capacity of sub-station/capacitor bank f. line diagram
How select ELCB for 32amp. socket having quantity 12Nos. We have to do this wiring in PLANT. Please Also explain the incoming cable specification.
I am apply the AAI. So i want electrical sample question paper in technical with answer my id is vijayjobsmart@gmail.com