Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to rectify the problem ,if we erected the DPT instrument
wrongly of hp on lp side and lp on hp side?

Answer Posted / mr.georgemathews

It is a common mistake to connect the lp side to the hp side
of the DPT and the Hp side to the Lp side of the DPT. SO we
need not to worry.

The solution is to remove the impulse connection from the
DPT , make a 180 degree turn of the diafram, which is the
connection mode of the DPT. If u see it you can see there
are holes on the opposite side also (H & L). which is just
the opposite to front side(L & H). SO no u can connect the
impulse line out here. And also we better recalibrate the
DPT Using HART Communicator.

This whole process will hardly take 5 min.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

HOW TO CHOOSE FREAQUENCY IN FMCW TYPE RADAR INSTRUMENTS. DESIGN BASIS OR DESIGN CALCULATONS ?

2222


how 3 out of 2 Logic/interlocks works? give brief explanation with help of diagram.

2362


What is the difference bitween control net scaner and device net scaner

3631


if my flow is 20000 m3/h than which range of DPT i have to use????

1874


i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....

1514


what should he know if he is an assitent engineer instrumentation in cement industries of experience of 10 - 15 year.

2150


When doing a liquid seal on a differential flow transmitter , most of the time the sealing liquid will be heavier then the process fluid. For wich application will the sealing liquid be lighter than the process fluid if transmitter is mounted below the process line.

1863


what are the values of fuel flow rate in various places in boiler.

1770


Why is it necessary to use compensation leg to measure the liquid level in a closed or pressurized tank?

2520


Specify eight technical requirements that you would consider important, when deciding upon a particular control valve?

1941


How INtools is useful for routine Instrument maintenance?

2130


i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?

2270


Can anybody please let me know Orifice plate sizing calculation formula and step by step procedure

2031


Who to difference between analog in & analog out in dcs?

1747


Definition of reverse and acting controllers:

2373