Answer Posted / bhatt
As we know,capacity of conductor carrying conductor is
fixed in a perticular atmospheric conditions.Current in
transformer or DG set or alternators depends on load power
factor, current drawn by a perticular KW machine is more if
power factor is low whereas same KW rating machine wil draw
less current if it has high power factor.Hence
Transformer/DG/Alternator can not be designed for KW but
for KVA rating.It will feed high KW with high power factor
and low KW with low power factor without damaging winding
conductor/insulatin.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
How many types of electric motors are there?
Can we put 3 layers of cable tray while installing tray
What current position are you holding in your current company?
what is Fan Control Cubicle
what is meant by impedance & transient protection?
what is the min and max ohmic resistance for the earthing rod installed for lighting poles for street light network
what is the minimum voltage require to injure our body?
What is the dc grounding system and what is diff between AC/DC grounding system?
Which motor will you choose which can operate in both lagging as well as leading power factors?
We have two APFC panels in same station. I need how to connect CT in two APFC panels.can we take one CT in series connection or two separate CTs.
Hi,iam a diploma in electrical engineering.rtd from indian air force in apr 2007.prsently working in reliance next link as a network maintenance engineer since 2007,can i get a job in motherson sumi.
any one please tell taht what type questions will be asked in BHEL interview, i am having interview on 24th Dec, please send this to mail pradeepsistam@yahoo.co.in
draw vector diagram and +ve,zero sequence diagram of symmetrical three phase fault.
What is resonant peak?
what is mathed of check the D.C MOTOR 181 KW (ARMATURE AND FIELD) WHAT IS THE MATHED OF CHECK THE THYRISTOR MODULE (HIGH CURRENT)