I HAVE GOT TYPICAL PROBLEM WITH THE TEMP.INDICATION.
THE PROBLEM IS THE K-TYPE T/COUPLE OUT PUT IS CONNECTED TO
A INDICATOR.THE INDICATION FLUCTUATES SOME TIMES AND SOME
TIME IT IS STABLE.
WHEN I CHECKED OUT PUT OF T/COUPLE THE MV WILL NOT VARY.
WHERE AS INDICATION FLUCTUATES.
WHEN I GIVE MV SOURCE TO T/COUPLE EXTENSIONCABLE FROM THE
FIELD IT INDICATION IS STABLE.
WHEN GIVE MV SORCE TO INDICATOR ITS INDICATION IS STABLE.
PLEASE CLARIFY.
Answer Posted / aftab ahmed mazari
I agree with Mr. Satyendra Bhai Patel suggestions.
More over please check followings:
1. May be some electric motor starts and its cable routing
is near to your extension cable.
2. Also get check thermocouple,some time,its hot juction
got open and close with the passage of time. Replace
thermocouple.
3. Check loose connections.
4. Check thermocouple any wire being grounded at some time.
5. Any how, do not megger thermocouple extension wire.
Check it with normal multimeter.
aftabmazari@yahoo.com
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
Differentiate between ultrasonic flowmeter and radar type flow meter
What is difference between “Fault Tolerant” & “Fault avoidance” PLC? Application where these system s are used?
god evening sir i am studying m.sc(tech)electronics &instrumention.am i elegible to all industies
How oil line flow measured?eplain about instruments used and working principle?
Do you have reference list?
what is the diffrence between pressure safety valve & pressure relief valve....pls
is there any digitel grevity meter availaible in the market by which we can measure specific gravity of a battery?
Capacitance, resistance ( colour coding ), parallel & series circuits.
What are the different types of thermistors used in industries? How to the operation of typical thermistor?
Pressure tx shows 1 mbar but we need 1000 mbar at this process condition .. how can we sort it out .
how will you check torque value during Factory acceptance Test for control valve/ESD ON/OFF VALE how will you confirm this torque value is being correct, Which document will you be refer.
How is PH sensor works ?
all types of liquid analyzer principle with drawing?
what is droop in governer ,type of droop ,how it work
What are the error values can accepted in flow transmitter calibration?could u give any formula for this?