Answer Posted / g pravin
at 4-20ma with +24V power supply, no spark will be
generated.& 1 VDC at 4 mA of loop current and 5 VDC at 20
mA of loop current as per standard of analog i/o cards.
if we use 0 to 20ma instead of 4 to 20 ma then we can not
find actual position zero reference output, for example if
we have a motorized valve, it's full close at that time we
get 0ma (0%) reference and at fully open position we get
20ma (100%) reference, in this condition if power supply of
is off then we also get 0ma reference, so here in this kind
of
Condition we can't get actual result like that gate is
actually close or any other problems as per explanation of
above
| Is This Answer Correct ? | 21 Yes | 4 No |
Post New Answer View All Answers
what is cold loop? difference between hot and cold loop?
How to check vortex flow meter is in good condition while we do not having calibration setup?
Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com
What is the procedure of calibration of Load cell?
Explain the working of rota meter.
in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.
What is solenoid valve? Where it is used?
Explain PID controller tuning & any one method used for it.
pls provide me syllabus and old question paper of instrumentation engineering for GET(JSPL)
Explain the key components of control loop?
please tell no. & add. of consultancy who recruit me in power plant as instrumen engg. present i m working in power plant as ass.t instrument engg. thanku mahesh 09226562826
how to check earthing,what is minum ohms for proper earthing
What is difference between ESD and PLC please Explain me clearly.
HOW CREATED LP & HP PRESURES IN DRUM FOR DRUM LEVEL MEASUREMENT!
Which Signal hart communicator work? If there any signal change when hart connect while transmitter in line ?