we have taken HV test of 2.5 k and Megger test on 11 kv HT
cable.here it shows no fault but when we are charging the
same cable with 11 kv supply why the VCB 11 kv gets tripped
can anybody define the possible cause of fault ?
Answer Posted / shariff
The 11kV cable will be designed for morethan 12kV and the
megger applied voltage is just 20% of that rating.. so the
cable insulation might be withstanding at that vg but it is
failing at higher voltage.. So go for the Hi pot test with
DC pulse nearly 15kV...
Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
what mean by analog ,digital,numerical meters and relays? say the example?
Please clarify 1. Icw: rated short circuit working withstand capacity 2. Icu: Rated ultimate breaking capacity 3. Ics: Rated service short circut withstand capacity 4. other specification of ACB
state working of halogen lamp?
Define de-sensitivity?
Mention what are the types of semi-conductors?
how we select ac fuse rating of an power inverter???
What should be the protection scheme for a 15kw, 3-phase motor working in a lathe machine.
Sir, I m 3rd year student 4m DCE and want to do internship in siemens or l&t or any other mnc related to electrical engineering. please tell me the procedure 4 same and oblige me
how to generator maintenance (A Check, B check,Etc)
what is booster? and how it is connected in a circuit?
What are the reasons for the parallel operation of transformers?
which protection used in power plant?
what are symmetrical and non symmetrical components in electrical installation.
Sir pl provide 5 year sample paper for post junior engineer(electrical).I have currently applied for junior engineer (electrical) on RRB Ajmer
For overhead protection we use which transformer?