can we replace a pressure transmitter of range 0 to 25
Kg/cm2 by a Pressure transmitter of range 0 to 10
Kg/cm2 ?.. Will it affect 4 to 20 mA output signal which we
will feed to the PLC.
Answer Posted / yashwant
yes, only make sure the pressure will never rise beyond 10 I
think its design for 25 in safety condition. if u wish O/p in
0-10 you can scale 4-20 ma as 0-10 at plc, no need to change
tx.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
please send the drdo exam paper
what are the values of fuel flow rate in various places in boiler.
Explain the combusion chamber
Describe the typical instrumentation used in monitoring the performance of a shell and tube heat exchanger.
sir i m preparing for BARC but i am not getting any papers to prepare for this exam so please send me some sample papers to my i.d for the preparation of barc.
how 3 out of 2 Logic/interlocks works? give brief explanation with help of diagram.
Specify eight technical requirements that you would consider important, when deciding upon a particular control valve?
What is the cascade control
What is the minimum rating availalbe for weld neck orifice in market?
How you calibrate absolute pressure with the calibration range of 0 to 1000 0C Absolute. Please explain the procedure for calibration.
how u calibrate sox nox co2 co in cemps?what is opacity n HPm?tell the standard parameters of cems?
can anyone tel the syllabus or previous year question paper for BHAVINI(EIE)2014.
Isometric drawings are generated during _________________ phase of a project
how to calibrate load cell
What is difference between “Fault Tolerant” & “Fault avoidance” PLC? Application where these system s are used?