Can we use 11kv Trivector Metre or Energy metre instead
33kv Metre at 33kv Over Head Line metering purpose?
Answer Posted / k.prakashchandra
The voltage input to almost all energy meters is 110 V line
to line ,which is the secondary voltage of PTs. You can use
them for all system voltages by applying the correct MF .
Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
What is Delta Connection? What is meant by Forward Delta & Reverse Delta & How Will be the Connection in Power Transformers?
What is clock position of Transformer?what are the clock positions are there?and what is different of them?
If one lamp connects between two phases it will glow or not?
How PADO software increase the efficiency of power plant?
How Can you do Maintenance of ACB of 2000Amperes
Why generation voltage in thermal power plant is between 11kv to 33kv?
single phase power supply give to separate one steel coup with water, what reaction create
Logic using 1 kV or 1,1 kV grade in house wiring Low voltage cable. Explain/suggest? some use 1kV and some prefer 1.1kV grade insulation low voltage cable why??
what is the correct method for the outdoor termination of 19/33 KV HT cable step by step?
1.ZEBRA conductor(large size) 2.KUNDHA conductor( small size ) 3.panther conductor(very small ) 4.lepard conductor (very very small)
why on axial hitting up of air blast on hydrogen produced in oil circuit breaker,temperature rises of the core of the arc?
How to calculate multiplying factor of dc energy meter
how to calculate the power factor when instantaneous voltage and current has harmonics in it ?
What will happen if we introduce negative feedback to a control system that uses a positive feedback?
Can RCD's used to protect the VVVF drive if not why.