Require Generator Capcity ( KVA ) for 3 Phase Motor having
4.7Kw with starting current of 16amps?
Answer Posted / asif.k64@hotmail.com
KW=KVA*P.F
4.7=KVA*0.8
KVA= 6KVA approx
However the starting current is 16A hence we require a DG
of higher capacity.
This can be achieved by using a 7KVA DG.
| Is This Answer Correct ? | 5 Yes | 1 No |
Post New Answer View All Answers
wat is d diffr btw shunt coil and trip coil in VCB?
what is the diference between the 4pole & 6pole DC Motors & what is advantage 6pole over the 4pole ?
How can a equal potential zone be carried out in conductors?
what is the effect of higher value of GD???
why steady state stability limit is greater than transient stability limit ? How it can be explained ?
What is the difference between grid and off- grid system??
What are the two basic types of transformers?
what is the benefit of floating our DC source? if i have two floating DC source of which 1 has a ref voltage of -21VDC and the other of -18VDC. can it be connected in parallel to share a common ref voltage? if not, how do i make both sources to be of common ref voltage? tks
What is the formula to calculate the rating of power cable for three phase current.
Star Delta Diagram with full description
WHICH SIZE A.B.CABLE IS USED FOR 11KV.
How to determine the breaking capacity such as break down current and break down voltage for VCB and CT's.
in indoor type circuit breakers why only the corner breaker trips specially during cold season. What is the reason.
100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.
please I wont know how to calculate the vector group for power transformer ZNyn11 best regard.