Answer Posted / noel
You should check that the alternator is aligned properly
with the generator motor. this should be done according to
the manufacturers specs. Rotate the alternator and check the
gap between the rotor and the stator. Also this should be
provided by the Manufacturer. Then take and IR and PI test
and record your findings. Check that the data is on the
right parameters. And also check the wirings for the CTs.
Depending if they are European or US manufactured the flow
of the current may vary a give you incorrect trips during
commissioning.
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
one split ac how can told of this ac which Tr tell me us
what is the use of surge suppresser in 33 KV incoming panel. where it must be installed,inseries with incoming cable surge suppresser must be at incoming of the breaker are outgoing of the breaker
What is the permissable nutral current of three phase system as per IS standards?
sir pls send the je exam - 2008 and other model question papers..
which pump used in STP
Draw torque - speed curve and load curve of induction motor? mark operating point ?
what curve and rateing would you use for a three phase 0.75kw motor?
Explain the operation of grid connected central solar inverter ?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
A 10 MVA, 66KV, 50Hz, Y-connected 3-phase alternator has synchronous reactance of 0.635 Ù. It is working at full load at 0.8 lagging p.f. condition. Find torque angle, neglect armature resistance.
Why neutral is not used in three phases dol starter
I NEED RRB APTITUDE QUESTIONS AND MODEL PAPER,PLEASE SEND MY E-MAIL joo28_eee@yahoo.co.in
EXPLAIN WHY THE SURGE CURRENT RATING OF AN MCCB OR CIRCUIT BREAKER DECREASES WITH INCREASE IN THE RATING OF MCCB OR CIRCUIT BREAKER.
what is the isolation transformer. what is the isolator?
working of diesel generator ?