i have one transformer 1000kva, 11/.433kv. we are using
200/5 amp. ct unit for measuring purpose, & one 800 amp.
V.C.B Unit for the same t/f operate, i wants to known the primary
current of T/F is only 53 amp. why we used 800 amp.
V.C.B ? & 200/5 amp. CT Unit.
Answer Posted / krishna chaitanya
first u must know that transformer transforms with
no change in power. As its 11 kv on primary side as
per funda you can calculate primary current 53 amps.
P = vi cos fi. A 100/5 ratio ct is enough to measure.
But its always advisable to select equipments with
larger than required ratings. Sometimes u'l see a
300/5 ratio ct.
and vcb, 800 amp vcb is for load. There'l be another
breaker at secondary of transformer with larger than
this amp rating. 800 vcb is provided for a particular
load control.
checkchaitu@yahoo.com
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
what parameters should we check to reduce the power bill
How to prepare electrical preventive maintenance plan & shedule of machine tools in manufacturing unit.
can mini-curcuit supply MIL-tested transformer !
how to protect motor in dol starter having capacity of 30 hp.40 hp?
Operation carried out in thermal power stations?
Difference between megger test equipment and contact resistance meter test instruments?
Brushes are placed at magnetically neutral axis,when brushes reach that point,the armature conductor gets shorted,but it can be seen that the dc supply is also shorted,wont that get damage? help me plz
Does all the output contacts (N/O as well as N/C) of a Numerical relay operate when relay receives a binary input/inputs or contacts are designated to specific logic input/inputs and only these contacts operate?
what are the differant std sizes of cable trenches?
compare between starting charactristics of synchronous motor with those of 3Q Squirrel cage induction motor
what is thermal resistance of PVC Cable.
what are the major & minor faults that occur in an inverter and in UPS ? And how to repair and resolve them ?
what is electrical machines
What are approaches to tackle sedimentation problem of reservoir?
How to calulate Locked rotor amper(LRA) for compressor type motors?