i have one transformer 1000kva, 11/.433kv. we are using
200/5 amp. ct unit for measuring purpose, & one 800 amp.
V.C.B Unit for the same t/f operate, i wants to known the primary
current of T/F is only 53 amp. why we used 800 amp.
V.C.B ? & 200/5 amp. CT Unit.
Answer Posted / krishna chaitanya
first u must know that transformer transforms with
no change in power. As its 11 kv on primary side as
per funda you can calculate primary current 53 amps.
P = vi cos fi. A 100/5 ratio ct is enough to measure.
But its always advisable to select equipments with
larger than required ratings. Sometimes u'l see a
300/5 ratio ct.
and vcb, 800 amp vcb is for load. There'l be another
breaker at secondary of transformer with larger than
this amp rating. 800 vcb is provided for a particular
load control.
checkchaitu@yahoo.com
Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
why should small green grass ans small plant should not be there inside the transformer Yard in the factories
Why armature rheostat is kept in maximum position?
how can i reduce sparking without stepdowning the voltage
some time we open engine breaker 8.0 MW load but plant not trip. and another time engine open 4.0 MW load engine trip why? individually engine breaker open & individually emergency stop why difference?
What is T’Q and X’Q and X’D ? and what is saturated as well as unsaturated ?
what is ratio of copper wire size and current ?
how to operate and maintenance of 1500 kva diesel generator set
at what basis/standard we have to arrive the current density of aluminium/ copper in busbar?
What does ampere turns shows?
Is there a diode made that works with AC 120 volt 20 amp? If so can it completely stop all current flow in 1 direction at all times?
what are the sample questions asking to the test cunducting for electrical superwising lisence test?
we have 3 single phase transformers. how will we generate 6 supply from 3 phase supply input
What is the lifetime of a Thyristor? Is there a recommended lifetime for thyristors after which they should be replaced?
how many Classification of fire extinguisher