Dear All,
In a 400V power system, ratio of three current transformers
installed incoming switchgear is 4000/1. Maximum three
phases short circuit current of this system is 48kA. One CT
is installed on neutral of upstream transformer (6/0.42kV,
solidly earthed) for 51G protection. Would you please inform
me about the correct CT ratio of this current transformer
(on neutral)??
Thanks a million
Answer Posted / k.prakashchandra
Further you can not expect much earth fault current in
neutral earthing as the voltage is only 230.Unless the phase
comes in contact with earthed metal part or welding is done
on the ground, this current will be too low to be picked up
by ct.As the power supply points are provided with fuses
,the relay may not get a chance to act at all.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Comment on the working principle of operation of a single-phase transformer.
Is potential difference materials property ..? if yes tnen how.. explain brifly.
Why neutral point is consider as zero potential?
What is the physical significant of power factor?
what is the common earth
How phase to phase voltage comes 440V.
What is the purpose of stablization resistor in high impedance bus bar protection
Please brief what is sinewave
what is the function and use of cable differential protection relay?
how to calculate units consumption for a 12 hp motor /hr.
Either It Possible a dc Motor to Run On Ac Drive [ Ex : ACS 800 , Yaskawa F7 ] If it is Possible How Pls Inform Me dinesh_elect_eng@yahoo.com
PLEASE INFORM ABOUT THE IDEAL TEST RESULTS OF MAGNETIC BALANCE TEST OF TRANSFORMER 33/11 kv DELTA-STAR T/F
what is stper motor
mention hazard experienced during installation
wat is the first thing dat is needed, 2 lay a cable in some area??