At site, we have 30Kw motor (3 phase, 400V,50Hz) and FLC
54A as per the nameplate. At the time of starting it draws
840A instead of 390A (7.2%). As per the data sheet also its
390A starting current. it thru a dol starter from the MCC.
can anyone tell what is the problem in the motor

Answer Posted / wani y.s.

First Check the healthyness of the motor -

1. Check the winding resistence
2. Check insulation resistance using megger.
3. Check the bearing and apply the lubricant as applicable.
4. Check the healthyness of connected load.( It should not
locked etc.)
5. If all above is OK. Then remove the motor from load &
ensure it is starting in ideal condition.( Hope connections
you are following up as given on the nameplate)
If it is starting in no load that means load GD squre is
high. Motor is taking longer time to start.You have to
select proper heavy duty DOL starter to withstand the
longer starting time. But ensure that motor is having
thermal time capacity to withstand this time.
7. You can also go for VFD as a starter this will definetly
will solve your problem no need to take care of thermal
time of the motor. Only select proper VFD to suit starting
torque of your application.

Is This Answer Correct ?    0 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

is it possible to test of bus bar in high rise building without completed full floor ?

1183


Whar is the KvA rating of 33Kv substation & actual kv rating of power generaating station.

1889


how to calculate regulation constants for over head lines? and what are the regulation constant for raccoon conductor at different voltage level and different P.F?

1469


how to CHECK CT AND PT AT THE FAULT OCCUR IN GENERATOR RELAY PANEL .

1752


How impulse levels are calculated that for 11kV impulse is 75kvp, for 24kV impulse is 125kvp ?

1556






Why single phase induction motors are not self starting ?

1063


How does the slip regulator works as a startor

1505


what is EIB lighting control system? what is the advantages of this system?

3210


The knee point of a current transformer is normally unique and known.So why in the nameplate of a CT they put the minimum value like this Vk> 400v.

938


I am going to appear for the RRB Chennai junior Engineer online exam. Please send me the previous exams question papers (also solved) to my mail id: rrkhandhar@yahoo.com

1527


Where should the lighting arrestor be placed in distribution lines?

672


Apparent power is expressed as V * I(Conjugate). Why not in V * I ?

3457


In general bus riser follows the bus section in SWGR. What are impacts if bus section follows bus riser?

1089


How to calculate the time setting for star connection in star delta starter? For example 10KW 3PH Induction motor.

2160


what is the path of thunderlightening? once both a buffalo and a person were standing 5m apart but lightening hit and killed buffalo not person?

2450