Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

control valve in manual/auto mode huntting checked spring
tention also it is ok.positioner also good condition &
incoming inst air line also constant pr.kindly give us
correct answer?

Answer Posted / ashish namdev

Kindly check these following :-

1. first check positioner link spring.
2. adjust link assembly.
3. adjust instrument air at valve specified pressure
through AFR.
4. check all parameters and settings in positioner.
5. give auto calibration command and calibrate it.
6. Tune your controller.(gain, PID controlling)

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the use of GMV in turbine?

4416


Explain about safety integrated level protection? . How it was differ from other protections ?

1738


What is the basic difference between Modbus and CAN Open Protocols

6432


How addressable fire systems work? Pl. send details with architect.(Loop), also send details regarding Gas system. Pl. help me.Thanks

2097


what is the minimum power (P=VI)to produce a spark?

1974


How flow can be measured with dp?

1131


How to Calibrate Radar Level Transmitter in Field

1237


Which is the best field foundation bus. ( FF ) Yokogawa, Honeywell or others ?

1786


What is three element drum level control system why its better than single element?

2561


any questions on motor and energy conversions machines?

2221


Somebody can explain me about >Critical Loops, calibrations, ESD critical Loop checks, Logic Diagram / Cause & Effect checks for ESD loops,

1679


How is automatic reference junction compensation carried out in temperature recorders?

1086


what is the procedure of O2 sensor(ABB) calibration?

2179


Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...

2337


why we should maintain neutral earth voltage below 1V while calibration? why cant it be 1.2V or 2V

2426