How can decide the MVA rating of power transformer for
substation like 220/132, 132/66, 66/33kv etc or even higher
kv rating of substation????
Send me the strictly technical answer that shows your strong
technical aptitude.
Answer Posted / j.karthik
The MVA rating is only based upon the generating MW capacity
of the plant.
For Example:
50MW is generated in the Powerplant.(i.e. Generator
capacity is:50MW,11kV,0.8P.F,3000RPM)
Now we like to connect this 50MW power to the E.B.grid
then we use one Step UP Transformer i.e. to step up the
voltage from 11kV to 220kV.
Now we can calculate the MVA rating of that step up
transformer as:
i) MVA = MW/costeta
MVA = 50/0.8 = 62.5MVA.
This is the answer.....
By,
Karthik(Engineer)
| Is This Answer Correct ? | 11 Yes | 7 No |
Post New Answer View All Answers
how to check ac servo motor
How to decide the size of the capacitor for a single phase induction motor say 2 HP ??
how much allowable resistance that can be difference in motor all coils?
how single phase preventer works ?
Whether amorphous core transformer is available in India?.If available then up to what rating of voltage and KVA?.
The power supplied to a 50mH inductor from a 120V, 60Hz source will be
what is the efficiency of thyristor
how to apply b license to c license in tneb
why can we use cosine wave instead of sine in ac supply as both have same rms vale and ripple factor
how is control wiring coding is done in a CRP panel ?
WHAT IS counter flux IN CT?
I want to design a heating coil of 80/20 nicrome for 3.5KW please give me the calculations choosing for physical dimensions assume coil voltage will be 110V AC assume necessary conditions
what is the meaning of number in (11, 31, 61,14, etc. CDG11, CDG31, CDG61, DDT32
what will be happen if earth point is being used for as a neutral point for raw power , and same will be used for ups earthing
How to calculate the sag of OPGW during stringing???