How to calculate the ups battery back up? give the formula.
Answer Posted / sathiyanarayanan
backup formula= KVA/DC LOW *POWER FACTOR
FOR EX:2 KVA/120 DC VOLT(SYSTEM VOLT)OUR MAINTAINED POWER
FACTOR (0.8 P.F),PER BATTERY=12V(DC LOW=10.8),HERE USING THE
SYSTEM VOLT=120V SO,10 BATTERIES-10*12=120V
DERIVATION : 2000/108*0.8
AH=14.81(APP.17 AH BATTERY) given 30 minutes backup
| Is This Answer Correct ? | 7 Yes | 8 No |
Post New Answer View All Answers
what is the power factor used by the PHCN in nigeria? 2. what is the difference between an alternator and generator. 3. Generation of poweris in KV but how is transmission is in MW. 4.If the transmission of power is 20,000MW how can it be increaesed to 80,000MW
Anybody know how schematic diagram for reverse power relay? RPR for generator protection
What is hipot test procedure?
what is the reactive power what is the use of it in system
Is there any standard guidelines/Criteria to design NGR/NGT.?
How to test the vector group of a Yd11 transformer? what are the relations to be checked between various vectors to confirm this vector group?
At full load wat is the motor p.f And at no load will is the motor p.f?
Why temperature rise is conducted in bus bars and isolators?
when it is possible kvrah lead & fundamental kwh be equal in electonic trivector meters (3 ph)
I want to calculate how much capacitor we connect to maintain the unity power factor? Is there any formula? Pls give me the answer
What is the need for a controller?
A 400 V, 50 Hz, Δ connected synchronous generator has a field reactance of 0.1 Ω and armature resistance of 0.015 Ω. At full load, the machine supplies 1200 A at 0.8 pf lagging. Under full-load conditions, the friction and windage losses are 40 KW and the core losses are 30 KW. What is the machine’s overall efficiency? Ignore any field circuit losses.
Brief me about maintenance planning & sheduling of machine tool.
What is A check, B check, C Check & D check for a diesel Generat
what is spadar bar .why I use in DC generator.