Dear All,
In a 400V power system, ratio of three current transformers
installed incoming switchgear is 4000/1. Maximum three
phases short circuit current of this system is 48kA. One CT
is installed on neutral of upstream transformer (6/0.42kV,
solidly earthed) for 51G protection. Would you please inform
me about the correct CT ratio of this current transformer
(on neutral)??
Thanks a million
Answer Posted / k.prakashchandra
The maximum earth fault current occurs when the phase comes
in contact with the earthed metal part.That will be about
230/0.5 i.e. about 500 A ,ignoring impedance of tr and
taking ER as 0.5 ohms.It is the usual practice to set EFR at
20% of OCR setting.For REFR the CT ratio should be the same
as that of phases.You can have a 2 core 4000:1 NCT and set
the 51G at 0.1 to 0.2 In ,using one of the two secondaries.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
A 2083kva AVR was tested, phase to ground shows continuity, what is the implications
How it can worked plc based electrical system And which type of software using.
why don't we use the generator as a motor? and what will happen?
why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?
I have 2500KVA transformer delta/star,13.8KV/380V provided with LV 4000A breaker. Already I have 2300KW motor feeder with a full load 90%. Is it possible to connect another 1600A from that breaker? If so how the calculation is done?
What is the minimum distance to be maintained in between HT panel and LT panel and Instrument panel as per IEC and NEC standards?
In vapour absorption refrigeration machine fluids used are
What is value of earth resistance required for substation and equipment earthing and what are the reference guidelines
Why choke coil is connected in series with starter in tubelight??why starter is connected in parallel to tubelight??
How to configure the drives in PLC, through Profibus commnication. And to how to address it?
HOW TO DESIGN THE body EARTH cable(Copper Conductor) size for 60KVA UPS?
1- What is the Polarization Index number be good for 15KV 3c#500MCM electrical cable? 2- Can I use the IEEE Std 43-2000 to perfom the PI test? Thanks
The power supplied to a 50mH inductor from a 120V, 60Hz source will be
How to calculate Ith (I thermal) for curent transformer
What is routh hurwitz stability criterion?