hello dear
i have faced problem in drum level transmitter.
the problem is when i engrize the meter meter shows 100%
but the actual level 40 or something plz suggest me
Answer Posted / yomama
The impulse tubes must be filled with process fluid or fill
fluid such as glycol. Additionally the specific gravity of
the fill fluid must be calculated in reference to the
process fluid being measured
Glycerin (Specific Gravity=1.26) for the impulse tubes a
correction must be made.
DP span of 100”= physical height difference of impulse tubes
on vessel
SG of fluid being measured (Oil = 0.68)
Glycerin filled tubes (SG = 1.26)
Since the Low Pressure Leg will be filled with Glycerin we
multiply the span by the SG of the Fill Fluid
100” x 1.26 = 126” so the Lower Range value will be -126”
Span will be the LRV – (SG of fluid) x ( tank Level span) = 68”
-126” + 68” = -58”
-126 LRV
-58 URV
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is difference between ESD and PLC please Explain me clearly.
what is easiest way to read STL language in PLC?
How can i copy program (parameter) from mm440 (V.F.D.) by using BOP?
what is the process for double acting cylinder pneumatic for 32' v/v
Explain about the leakage class of the control valves
Explain the mechanism behind the turbine meter.
How to calibrate level transmitter with use of HART?
Where Can i take a SPI INtools training in Mumbai? In Rolta India Ltd to whom I should approach regarding of SPI INtools Training?
Instrument QA/Qc what is the project quality plan?conduit inspection RFI. which documents attache with package?
how pressurize drum calibrated ?
A flange is used for instrument connection for a system with a design temperature of 316C (600F) and a design pressure of 1000 kPa (145 psi). What is the class rating of the flange to be used for this application? Explain your answer
hi! i want to know about mpse exam.
is there any digitel grevity meter availaible in the market by which we can measure specific gravity of a battery?
what effects a surging can produce in the compressor
I am having a Phoenix digital to modbus converter. The o/p of the same is connected to flow computer FB407. But the digital signals are updated only after one minute in the flow computer. what may be the cause of delay in communication? Flow computer is having a scanning period of less than 1 sec.