what is procedure of calibration of remote seal
transmiter, botom to top flanch 850mm, fluid liquid
density .73, transmiter fixed on a fractionation colum,
under vaccume 10mbar
Answer Posted / yomama
Your question suggest you are using a "Differential Pressure
Transmitter" in which case since the -10 Bar vacuum is
applied to both the Hi and Low legs the -10 Bar vacuum is
neutral the Transmitter
In that case we merely multiply the distance (850 mm) x (.73
SG) = 620.5
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What are the interlocks we have to check during the start up of LP/HP compressor?
what is the difference between active & reactive power?
What are the different types of thermistors used in industries? How to the operation of typical thermistor?
what is the difference between -24 : +24 & 0:24 and where it use?
how will you check torque value during Factory acceptance Test for control valve/ESD ON/OFF VALE how will you confirm this torque value is being correct, Which document will you be refer.
selection of the zener barrier for the hazardeous area zone 0
Hi, Is there any smart plant instrumentation design training institute in Bangalore?
hello can yoy pls send me previous papers of jindalpower and steel ltd.....'m from instrumentation..... mani1048@gmail.com
WHAT IS MEANT BY PROJECT MANAGEMENT STRATEGIES IN INSTRUMENTATION?
what does the ratio 800-400-300-200/1-1-1-1-1 in the specification of current transformer indicates?
Explain why use mmwc unit?
What is intrinsically safe system?
WHAT ARE THE INSTRUMENTAL DIAGRAMSOF VALVES?
can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.
What is difference between radial vibration and axial vibration explain in detail .