hello dear
i have faced problem in drum level transmitter.
the problem is when i engrize the meter meter shows 100%
but the actual level 40 or something plz suggest me
Answer Posted / yomama
The impulse tubes must be filled with process fluid or fill
fluid such as glycol. Additionally the specific gravity of
the fill fluid must be calculated in reference to the
process fluid being measured
Glycerin (Specific Gravity=1.26) for the impulse tubes a
correction must be made.
DP span of 100”= physical height difference of impulse tubes
on vessel
SG of fluid being measured (Oil = 0.68)
Glycerin filled tubes (SG = 1.26)
Since the Low Pressure Leg will be filled with Glycerin we
multiply the span by the SG of the Fill Fluid
100” x 1.26 = 126” so the Lower Range value will be -126”
Span will be the LRV – (SG of fluid) x ( tank Level span) = 68”
-126” + 68” = -58”
-126 LRV
-58 URV
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is difference between Ionization heat and bimetallic heat
what is intrinscily safe system and where we use?
What are different types of orifice plates?
Which is the best field foundation bus. ( FF ) Yokogawa, Honeywell or others ?
what is the calibration procedure for magnetic flow meter @ onsite
plz you help about Que paper of mahagenco previous your,any model paper relad to it{maharastra power genration}
, Instrument Index, P&ID review, I/O schedule, datasheet, DCS / Analyzers specifications, loop diagrams, hook-up drawings.
State bernoulli’s application.
why using negative supply for bentley nevada vibration system ?
Can any body help to get Rsemulator 5000 free from internet if possible then give me any link or any help .
State some of balance principle’ advantages?
How to calibration coriolis flow meter?
I have energy meter for educational project having 0.5s class but my friend need 0.2s class meter , which one is good for that purpose and what is the actual difference of that two classes , need very easy example also.??
can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.
WHAT IS TMXT IN TEMPERATURE FOUNDATION FIELDBUS.