Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how we can select a transformer based on a particular load.
suppose we have 4 motors of rating 40 h.p , 50 h.p, 80 h.p
& 100 h.p. then what rating of transformer we can select.
urgent. pls reply

Answer Posted / ramesh behera

Here the g0hpiven motor values are
40HP,50HP,80HP,100HP
so total HP of motors are
40+50+80+100=270hp

1hp = 746watt
so 270*746=201420w
or 201.42kw

201.42*.85=251.744kva

Some power in hand so we should use 260kva single phase
transformer for these motor load

Is This Answer Correct ?    4 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How npn and pnp transistor works

1144


Why LED light has advantage of rapid reflection ,although other lights alse reflect.? and this light is considered to be best for transmission usage in case of Free optics

2047


why three phase capacitor takes unbalanced current in capacitor bank?

1497


What do you mean by the zone of protection?

1097


Rules and standards of electrical control wiring ?

1158


Why derivative controller is not used in control systems?

1194


what is acceptable leakage current for 33kv cable while doing high voltage test for cable? how to calaulate the leakage current for 33kv or any rated cable?

4039


sir vizag steel ka junior trainee ka paper kitne number ka ayega

2249


What is the test block protection relay if any body know plz explained

1487


Starting times for soft starter & power factor is thier any standard or datas available in manufactures list. Kindly suggest.

1941


What is the formula to calculate the rating of a three phase air circuit breaker

2333


I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?

1978


formula for calculation of switchgears(i.e. contactor, fuse, cb, relay etc.), if load current is given?

2214


why we change the direction of winding in rotor ?how we make the north and south pole?

2063


how to calculate compresor capacity?

2197