Answer Posted / nizam salih
A pole drop test can be done when the generator is in
standstill condition. Provide a ac voltage of 230V to the
rotor terminals of the salient pole machine and measure the
voltage drop in each pole. At least 5A should flow through
the rotor poles. A small current will not provide good
results. Once the voltage drops are recorded calculate the
drop index as follows.
Index = (max. value - min. value)/avearge value *100 %
An index value of less than 5% reprsents the poles are
good.
This is the usual annual test that we carry out in our
hydro generators.
Nizam Salih, Electrical Engineer, Sri Lanka.
Is This Answer Correct ? | 10 Yes | 2 No |
Post New Answer View All Answers
what is W.T?specify the acceptable range?
Is it good to short Neutral and Ground in the PLC or DCS main Power supply. Pls give YES or NO with reasons...? Simarpreet
How many types of electric motors are there?
why the field winding in dc motor is not short circuited eventhough dc supply is applied across the winding
i need the curve duty cycle and amper for (150 kva @50% dyty cycle) transformer turn ratio :19 and vin 400
how does grading rings & spacers in transmission line works? Working Principle?
Distinguish between nuclear power station with thermal power station for initial cost, starting period, cleanliness, and transportation of fuel
What are the advantages of using distance protection schemes as opposed to normal overcurrent/ earth fault protection on high voltage feeders.
how we calculate the withstansing current capacity of wires&cables?
what is ramping rate of generator
Mention what are the types of semi-conductors?
When the relative speed between the magnetic fields of stator and rotor does is zero under steady state operation?
how to calculate magnetic force genrated by a coil ?
Explain about retrofitting of machine tool.
Why we cant store an ac power. If we coo store in which device we can?