Answer Posted / nizam salih
A pole drop test can be done when the generator is in
standstill condition. Provide a ac voltage of 230V to the
rotor terminals of the salient pole machine and measure the
voltage drop in each pole. At least 5A should flow through
the rotor poles. A small current will not provide good
results. Once the voltage drops are recorded calculate the
drop index as follows.
Index = (max. value - min. value)/avearge value *100 %
An index value of less than 5% reprsents the poles are
good.
This is the usual annual test that we carry out in our
hydro generators.
Nizam Salih, Electrical Engineer, Sri Lanka.
| Is This Answer Correct ? | 10 Yes | 2 No |
Post New Answer View All Answers
is it possible to turn on the single phase star delta on delay timer using 24 v dc ?
why swityard is necessrry requirement in any bis power distributin systems?
Pls Breifly explain about UPS (Inverter,Reserve,Rectifier,Float voltage,Boost voltage).
how did i get the competency certificate as electricle supervisor. iam completed my b.tech.but i dnt have any experince, this certificate is required for applyng ongc mangement trainees. what should i do sir please suggested me
where solid grounding and where grounding through ngr done and why?
What are the section criteria for cables. Now everywhere XLPE power cable is used or PVC is also used?.
sir vizag steel ka junior trainee ka paper kitne number ka ayega
What is proportional controller?
what is the difference between ac motor and dc generator
Why human body feel electric shock?
What are the necessary solutions needed to be carried out on a malfunctioned earthing mechanism of a VACUUM CIRCUIT BREAKER.(TAMCO)
How to calculate Temp from Resister from PT100 equation,
What are locations arc protection relay is fixed.
WHY L-G FAULT IS MORE SEVERE IN TERMS OF RRRV?
what is errection pcbs?