If a Power Transformer Fails and the transformer
manufacturer suggest that "Do all electrical test on the
transformer?".
What are the test to be conducted in this condition?
Answer Posted / k.prakashchandra
Let me cite an example.We have one 220/110 KV 100 MVA Auto
transformer.After 5 years of service ,it tripped with a
sound, on the following relay
indications.Diff,OS,Bucholtz,OC -R ph and EF (REFR not
provided).On meggering without test charging ,the results
were OK with LT R -body being higher.Then we resorted to
continuity test ,which indicated that LT R phase bushing
has been open circuited.On examination it was found that
the joint in the lead from R-phase winding to bushing was
severed due to bad workmanship.We did not conduct any other
tests.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Hi Everyone ! My Name is Hakim ullah khan please i need formula of Cable Rating because i want to calculate by self without check any Table Chart... Thank you.....
How we can determine short circuiting current any plant and for example a plant which power generation is 415 volts and plant load is 500 kw.
How you calculate the repturing capacity of a HRC fuse
how will reduce the voltage. if 12volt/250ma transformer toreduce 6 volt
How to control motor gearbox speed and friquency? If length of cable and dia given, how to measure the voltage drop?
what is data block in plc ? How the values of data block are written and read by hmi ? what is the difference between function and function block ?
What is the difference between circuit breaker and isolator
how we control automatic generator i'e with to supply (main supply and local generator) when the main supply was break to supply the local supply automatically to begin supplying power.I now this control circuit is the combination of contactor time delay contactor switch and overload relay .but my question is how we combine those component thank you
How you will determine the volume of oil in a particular Distribution transformer.
what is the difference between transformer,converter and transducer
Why 30kw 40 hp 4 pole 3ph induction motor over heated?any steps on reduction in heat?
PLZ EXPLIN ABOUT CLASS PS CLASS CT .WHY THEY R DESINED AND FOR WHAT PURPOSE?WHY OTHER CT CANT BE USED AS PS CLASS CT? EXPLAIN IN SIMPLE LAUNGAGE IF POSSIBLE PLZ GIVE CIRCIT DIAGRAM?EMAIL-RAJ_SINGH_0376@SIFY.COM
if we have a industrial load of 400 kilowatts with 415 volt AC then how much total harmonic distortion (thd%) should be acceptable for steady power system.
-What should be minimum value of insulation resistance and maximum value of earth resistance at any electrical instillation and what is method of testing the same.
What is an iron loss or core loss pi?