If a Power Transformer Fails and the transformer
manufacturer suggest that "Do all electrical test on the
transformer?".
What are the test to be conducted in this condition?
Answer Posted / k.prakashchandra
Let me cite an example.We have one 220/110 KV 100 MVA Auto
transformer.After 5 years of service ,it tripped with a
sound, on the following relay
indications.Diff,OS,Bucholtz,OC -R ph and EF (REFR not
provided).On meggering without test charging ,the results
were OK with LT R -body being higher.Then we resorted to
continuity test ,which indicated that LT R phase bushing
has been open circuited.On examination it was found that
the joint in the lead from R-phase winding to bushing was
severed due to bad workmanship.We did not conduct any other
tests.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Can any one provide the inspection procedure of MIMIC for VFD panel? Details: If someone wants to have a mimic in the VFD panel what are inputs considered for the mimic(like on,off,trip) whether we are able to add speed variation in the mimic(if so how can we get) and what are the parameters to be checked in the MIMIC during inspection?
Enlist four components of electrive drives.
What happens to a line-frequency of high-frequency transformer when it is first energized/ re-energize?
in my working site. momentary jerck in electrical supply ocurred frequently which cause of multiple losses in our electrical equipements. how can we protect our electrical machines and equipements in this situation.
Please, if 1kw is equal to 1.25kva; how then do I know how many kva in 7.5kw?
how dia of wire and angles are calculated for overhead shielding wire to protect substation equipment from lightening strokes???
What happened when voltage will half value of current ...
What are diffrent type of road taxes?
What is the relationship between voltage,current & frequency?
What are the differences between single phase and three phase?
What is the difference between vector surge relay (78) and Pole slip relay (98G)
what is the difference between interconnection and intraconnections in the circuit diagrams
How much should be the load percentage for 15kva Inverter and Iinut & I output load with Calculations
how we can set the IDMT relay.
How to calculate approximate load loss of a distribution transformer by knowing %ge imp of transformer?