Control Valve is final control element of clost loop. So
signal coming to control valve will be in pneumatic form
but depends on size of Valve. It can be 3-15 PSI or 0.2 -
1kg/cm2 but it is not fixed. There is one instrument called
Positioner which will convert 3-15 PSI signal to desired
siganl depending on Control valve.
For any Contol Valve signal will come from Control room in
the form of 4-20 mA. this 4-20 mA signal was converted to 3-
15 PSI signal by instrument called I/P converter. This
siganl will go to positioner and the positioner o/p is
given to valve actuator to get desired opening and closing.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Why the ammonia and Nitric Acid level indicators is with millimeter ? and What is the conversion form millimeters that level indicator indicate to weight ?
how to calibrate load cell
what is Best Among SINK Or SOURCE Type Design In Digital Signal, Either Iput Or Output? WHY?Can any one..
How to Calibrate Ultrasonic Level Transmitter in field
What happen if I install my pressure transmitter below the elevation of pipe in natural gas service?
when a magnet is heated?
What is the meaning of wet leg
Coal mill Instruments Equipments for cement plant And process diagram ?
Draw a great bridge circuit.
in differential pressure transmitter,min&max pressure range for hp&lp
What is the advantage of using locally fabricated hook ups over Pre fabricated hook ups in process instrumentation?
OBJECTIVE TYPE QUESTIONS OF ANALYTICAL INSTRUMENTATION
what is the difference between magnetic flow meter and mass flowmeter
Explain signal isolator
Which types of quections asked in interview for FORMULATION PLANT (PHARMA)