What happens if a three phase induction motor is suddenly
single-phased while running? Which type of winding
connection will be affected?
Answer Posted / madhusudhana
A three phase motor will continue running if a phase is
lost. Most three phase overload relays are not intended to
provide true single phase protection, so the most likely
scenario is the motor will run at reduced speed for some
time and will eventually overheat and fail. A three phase
motor will not start, on its own, with only single phase.
However, if the motor shaft is "manually" spun it may begin
to turn and accelerate slightly. If the motor shaft is
turned backwards then the motor would start in reverse.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
fuel-air ratio in a petrol engine fitted with suction carburettor,operating with dirty air filter as compared to clean filter will be
what is smart grid? why we use it? explain in detals bcoz i want give presentatin from it....
How to calculate the value of earth capacitance in a transmission line.
concept of busbar and load dispatching..?
How to test Alternator stability test for REF relay
What happen if we apply square wave or traiangular waveform voltage to the transformer primary winding instead of sinusoidal wave?
how to decide choke rating for drive?
What is the basis for framing the rules of block diagram reduction technique?
What is the difference between resistance grounding system and resistance earthing system?
Can the output voltage of a rectifier be greater than the input AC voltage without the use of any voltage multiplier in the circuit??please provide the explanation too..
I have a situation to design sub-Distribution board/Panel meant for feeding power sockets. In the incomer CAN i Take TP MCCB with Neutral Link and All the outgoing feeders with to sockets with TP MCCB and Neutral Link? P.S : My System is IT Earthing
we have 15 ampere variyac but we want 30 ampere variyac what we do
What is the power requirement of tamil nadu for one month?
What is power factor why we should maintain the power factor unless what will happen
what is ramping rate of generator