Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

If a Power Transformer Fails and the transformer
manufacturer suggest that "Do all electrical test on the
transformer?".
What are the test to be conducted in this condition?

Answer Posted / k.prakashchandra

Test No. 1 and 8 belong to life evaluation tests.As the tr
has been in use, tests No. 4 and 5 may not be necessary.For
Inter-turn short, test No .2 may prove useful if the
previous values are available and magnetic balance test (
No.1 )is really useful.Oil test is just for knowing the
present condition.If the tr has failed within the guarantee
period , we have to take extra care while furnishing the
test results. The firm may put the blame on you,for the
damages for applying the voltages to test.Simple tests and
relay operations are sufficient.It is more difficult to
prove that a tr is healthy by all means.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what reason of line current and phase current in star connection and line current and phase current not equal in delta connection?

2093


what is the k var ratting of 1250kva

2094


Explain the following and how these are working with PLC Unit 1 I/O Module Card 2 Adaptor Card 3 Ribbon Adaptor 4 I/O bus 5 I/O Devices

1627


What is the estimated total hydropower potential of india?

1138


WHAT IS IEC? & WHAT IS BENEFIT TO PRODUCT FROM IEC?

2132


why we use ac supply as 415 volts instead of 415 v why we cant apply 230 v for dc

2408


What will be the fault current of any system when its generation is 10% of BASE generation( FUll Load )?Will is 10% or the same as full base calculation?

1917


why -48 volts dc used in telecommucation

2655


what is the minimum (Common factor) insulatin resistance of the following a, 4mm sq wire b, cable from 50 mm sq to 800mm sq

2108


how the testing of protection CT Testing done through Primary injection kit please describe in detail procedure...

2225


After completing iti in electrician, how can i get certificate of electrical supervisor? What ia requirements. For it?

1822


what are the applications of transistors with low dc gain, high dc gain and medium dc gain( beta)?

1777


Why does curving the pole faces in a dc machine contributes to a smoother dc output voltage from it?

1270


Refernce currents are to be generated using refernce cueernts how can this be done??

2004


if you are in a software company,then why do you want to come in a core company like sail, ntpc(where lots of trouble like tension but you have a good life in a it company) ?

1912