If a Power Transformer Fails and the transformer
manufacturer suggest that "Do all electrical test on the
transformer?".
What are the test to be conducted in this condition?
Answer Posted / k.prakashchandra
Test No. 1 and 8 belong to life evaluation tests.As the tr
has been in use, tests No. 4 and 5 may not be necessary.For
Inter-turn short, test No .2 may prove useful if the
previous values are available and magnetic balance test (
No.1 )is really useful.Oil test is just for knowing the
present condition.If the tr has failed within the guarantee
period , we have to take extra care while furnishing the
test results. The firm may put the blame on you,for the
damages for applying the voltages to test.Simple tests and
relay operations are sufficient.It is more difficult to
prove that a tr is healthy by all means.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
we have 2.2kw,Y,3000rpm motor but 6leads found in TB what happen if we connect in delta?
what is the difference between 4pole & 6pole DC Motors & give advantage ?
how balanced in star delta connection ?
Draw a SLD of DG distribution up to main LT panel?
Is neutral transformer can be called as control transformer?
What is 11 N1 and 12 N2 in single phase Transformer ?
how to find the torque of the single phase synchronous motor by doing an experiment
detailed procedure how we calculate cost for pcc m10 and rcc m20 including centering and labour excluding steel/ iron
Why induction motor is widely used in industry
Graphs of measuring power and speed on dc motor
what is the use of the circle diagram
What is the ratio of Booster transformer?
i need about 10 years of GATE solved papers in pdf format and even mock tests toooo
what are the possible reaons & remedies if resistance of NGR getting heat up
Haw to check conductivity of budbar