what will happen if the secondary of current transformer
kept open....
Answer Posted / gourav
Transformers operate at nearly constant flux. The principle
of transformer states that in order to maintain practically
constant flux the emf induced by primary produces a current
in secondary (if loaded), which thereby opposes the cause
as per Lenz's law. If secondary is kept open, there will be
no opposition to induced emf. The situation worsens if it
is Step Up (CT) as heavy current in primary (load current)
will induce dangerously high emf across secondary leading
to saturation of core as well as hazardous situation for
working personnel.
This can also be explained by B-H curve.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is the function of retrip in busbar?
why in a swquence network representation, the negetive sequence generated voltage is taken as zero?
what is the Pickup/drop off ratio in BCPU relays
if grounding is notdone at regular intervals for long distance transmission, will the load connected at distribution end receive voltage during negativehalf cycle of the sine wave?
why we setting 95 deg and 105 deg in wti and oti of distibution transformer ? give the reson for that ?
sourse is 66 KV / 350 MVA, transfarmer is 1000 KVA 6.6 / 0.415 kv, iF fault is 28.75 MVA on 0.415 KV Bus then calculat the Transfarmer Impidance
What is miller crystal oscillator? Explain its operation?
In Power Line Communication (PLC) the wave trap is used to block communication signals from entering neighboring lines. My question is this: Why do they allow for different filtering arrangements on these wave traps? Isn't it always going to be a low pass filter since we want the power frequency to go through, and the comm signal blocked?
how u measure/calculate renge of capacitor,capacitor has no any rating tag.what is the theory of measure of capacitons.
How to calculate the time setting for star connection in star delta starter? For example 10KW 3PH Induction motor.
If the feeder rating is 7.5 kw or 10 HP star-delta feeder, MCCB is taken as 63 a, contactors-32 a, how much will be the OLR rating or which range OLR should be considered when we concern about type-2 coordination?
We have studied about many techniques for finding the stability of system, ROOT LOCUS, ROUTH, BODE PLOT, POLER PLOT etc. In these which is used where. what are the difference among them... PLZ tell me.......
when will be the iocl interview results i faced interview on 8th september 2008 iam from electrical branch i faced interview for the post of electrical engineer??????????????????????//
What is different bewteen low or high impedance busbar protection scheme
can i use ups power as a raw power for another ups