What is the amount of no load current of 630 kVA tranformer
voltage ratio 11kV/440V ?
Answer Posted / dr. alaa baiumy abdel azim &a
frist we will get the rated current of the winding
I = 630 * 1000 / CUBIC ROOT OF 3 * 11 * 1000
I = 33 Amper
I NO LOAD = 0.5% OF I RATED
NO LOAD CURRENT = O.OO5 * 33
= 165 m A
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
Why GRR starts from 60% of motor speed why not less than 60%?
In diesel generator how AVR get voltage to excitation. And basic diagram DG EXCITATION CIRCUIT.
which type of amplifiers are used in multimete?
Where can I get Iidian straderd specifications for electrical items or works in web? please help me.
I want to put this query to SENIOR & EXPERIENCED ELECTRICAL ENGINEERS. 1)I want to know about the control circuit diagrams for control panels. I found it difficult to understand. Is there ant booklet through which we can learn the circuit diagrams? 2)I want to learn about conduiting, laying cables, preparing cable schedules and various techniques which is the part of building infrastucture(construction field). I don't have any experience in this area. I have experience in control panels only. that's why i am not getting any opening in building infrastucture (construction field).Can I get the job in this field as Trainee Engineer? How to enter this field? I need job in PUNE
What is difference between Sample test and Routine test in safety standard?
IN SINGLE PH TRANSFORMER IF LEKAGE IMPEDANCE DROP IS NEGLECTED ,THE FLUX IN THE MAGNETIC CORE and the lekage flux linking a winding are a)proportional to the applied v to the winding i respectively.
Why computer humming sound occurred in ht transmission line?
What kind of socket shall be provided for window type air conditioner with cooling capacity upto 18000 BTU/hr
diff. between tension mode & speed mode
what is RNG in the DG synchronizing by PLC?
. How to calculate the Short Circuit Impedance in Transformer? How to calculate the Short Circuit Impedance in Transformer?
What is the effect of pd controller on system performance?
I completed iti in2004 I was worked in A grade contractor can I get c licence
difrent between vcb acb sf6 and mccb breakers