Answer Posted / k.prakashchandra
If coil ends ( star-delta) are freely available you can
measure easily.If not (the primary windings are in delta )
,measure resistance across any two terminals and multiply by
1.5 to get the resistance of each winding ,which is the same
for the other two, for a healthy motor.If measurements are
done to trace the short circuited winding ,you get the least
reading across it by comparison.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What size cable (based on voltage drop) is required to supply a 40 A three phase boiler if the wiring system is 75V single insulated cables installed in non-metallic rigid conduit 56m from the main switchboard? Voltage drop in the consumer's mains is 8V.
What is meant by reactance voltage?
Vibromotor 252MV 1/4HP2P..what is mean by 252MV?
Why we use mho Relay in long transmission line?
How much should be the load percentage for 15kva Inverter and Iinut & I output load with Calculations
What is the formula for calculating the Instantaneous Short Circuit & overcurrent for any breaker
tell me some type of questions throught which i can prepare for exam and do my best
How do I calculate/select Droop CT ratio for various capacity of generators?
Grid fault level [KA]?
SUTIABLE FOR ohm's law super conductor
In the magnetic fluxes, what is the role of armature reaction?
can we do the star delta connection of capacitor for 3- phase motor starter.
sir i ve applied for hindustan petroleum and power grid india ltd..and the exams on feb 22.can you pls send model papers and tell how to prepare for those.i need to get into any of these for sure.....
state the working of discharge lamp?
1.what is meaning of curve into a mcb. 2.what is basic reason changing of curve