Hi ,what the accurate method to set correct(In) over load to
protect the 3~ motor
Answer Posted / pillay
I follow this method where before setting the overload
current setting I carry out an actual current consumption
test with a clamp ammeter.If the reading is lower than the
rated full load current of the motor I would set it at
actual reading add 5 percent and set it as the tripping
current. But if the the actual consumption is already the
rated fl current or almost it than the setting would be at
the rated full load current of the motor but never exceed
it.This way if it trips at any time than find out the root
cause and than only put into operation.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
What is FTA card? How it works?
A jet of fluid strikes a plate What was the force required to counter it?
What should be the height of basement according to NBCC code?
HOW TO CHECK THE VECTOR GROUP OF A TRANSFORMER YD11?
what is the requirement regarding earthing of Single conductor with AWA
are there rmu for 3 transformer?
How generator NPS(NEGATIVE PHASE SEQUENCE TEST)TEST WAS DONE? PROCEDURE WITH DETAILS?
Power factor =1.000 at factory in supply. However, PF = 0.8 at motor end. Current = 100 Amp, Voltage = 400 V. What is the power distribution loss? Can I reduce it by adding capacitor at the load feeder?
WHAT IS LOAD CELL
What is the rating of circuit breaker needed for 300 KVA load in 33 KV supply line in a transformer of 33 KV / 415 Volt ?
What is the suitable transmission voltage?
If i am running of spindle at 2000rpm ,but How to spindle stop at the second I am resetting the machine in CNC machines
Explain dc generator with its types?
Mention the disadvantages of low power factor? How can it be improved?
11KV AND 22KV NETWORK KW CAPACITY IN RING AND RADIAL?