what is 6 pulse and 12 pulse inverter? Explain brifly
Answer Posted / d.das
12-Pulse Inverter is essentially two 6-Pulse Inverters
supplied from transformer secondaries with phase shift. The
secondaries of the supply transformer are commonly chosen
as Star and Delta with a Phase Shift of 30deg. The 12-Pulse
Inverter is preferred over 6-Pulse Inverter due to its
inherent capability of suppressing third harmonic current.
| Is This Answer Correct ? | 8 Yes | 3 No |
Post New Answer View All Answers
What is nyquist contour?
why we are not giving the zone 1 trip command to the master trip relay
What is turn ratio of a transformer?
What is rotary phase converter?
What should be the voltage between Neutral and Ground in secondary side of the step down transformer (230 V to 110 V) with no load condition?
What is power relay?
If we have to feed a housing complex having load 8MVA, than what would be the better option, either we first step down 33kv supply into 11kv & than 430v or we proposed no of 33/.44 kv transformer, also which option is economical?
what is relation between ct and pt ratio with multiplication factor of a energy meter? is there any other factor on which multification factor depend?
- two pumps must work with them at the same time but if the first pump start the second pump must delayed for some time to start also , with motor rated power = 90 KW and rated voltage = 380 V and rated power factor = 0.85 lag please draw the power and control circuit for it and determine all circuit components parameters that you use it
what is high - pot test. what's its use?????
design a 3 bit synchronous and asynchronous counter using T- flipflop
Hi friends, i m electrical engineer i want a cdr for migration purpose so anybody have information about this then send me on jayesh_ee88@yahoo.com.please try to me
what is the size of cable for 15kw motor and 85 meter cable length using with vfd
any earth foult trip the relay but in welding time not trip by earth foult
For a 6.6kV Motor it is recommended to do megger test with 500 V d.c and not more than 5kV d.c but the Hi voltage withstand test should be performed by 12kV AC. Why the dc voltage test should be limited but AC voltage withstand test could be with such a high voltage?