what is the ground clearance of 400KV transmission line?
Answer Posted / k.prakashchandra
As per IE Rules 1956,for EHT line the clearance above ground
of the lowest conductor shall not be less than 5.2 m + 0.3 m
for every 33000 V or part thereof by which the voltage
exceeds 33000 V ,provided the minimum clearance along or
across any street shall not be less than 6.1 m. So for 400
KV line, it works out to be 8.8 m
| Is This Answer Correct ? | 49 Yes | 5 No |
Post New Answer View All Answers
what is electrical machines
Make a list observation on Transformer?
1))why we run three phase or three different circuit from a single conduit 2)) why not two circuit of different phase run in same conduit?? and why we run same three cicuit of same phae run in single conduit??
WHAT IS THE TOTAL POWER GENERATION IN CHHATTISGARH?
Can Anyone Answer anyone of these ? Q1) why direct SOLUTION of Load Flow Studies in Not Possile ? Q2)Why majority of Buses in power system are load buses Q3)Why one of the buses in Power system is taken as reference bus (slack or swing) Bus ? Q4)Bus Admittance Matrix is a sparce (means it contains some zero elements ) matrix , give reason
Define cuttoff frequency?
how to calculate the torque of a motor?
sometime battery charged and then automatically charged when rectifier ON conition, is there any chances please clarify the same.
Why sometime AVR and sometime Booster coil is used in Alternator? what is the diferance between AVR & Booster coil due to which they are selected
how to calculate the conductor size for certain KV transmission line and distribution line?
wat is d diffr btw shunt coil and trip coil in VCB?
What is the difference between isolators and electrical circuit breakers? What is bus-bar?
why ss stablity limit is more transient stablity limit?
Whether the vacuum contactor requires Short circuit protection?If No,why?
What is installed in PAC that is control the humidity