Answer Posted / mahesh sali
mostly total electrical cal.in KW at 0.8 pf as per thumb
rule.
KVA = KW/PF
as per nec code norms ur dg set shall be suitable to take
the higher inrush current during starting.
so awalys keep some say 115% to 125 % on induction motor
load.
for ups & lighting system around 200 to 300 %
Toatl kw rating = 1.25 * Kw ( Plant load )
KVA at 0.8 pf = Total kw/0.8
Assume that Dg set loading at 70%
i.e rated KVA = KVA /0.7
adding some 20% future load
i.e. actual DG ser rating in KVA = rated KVA + rated KVA *
20%
Thanks
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
how we can calculate chiller required ampear?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
what is v/f control in VFD?
area control error
Let me know that how i calculate the alternator sub tranciant reactance and tranciant reactance.
if a number of plc s are there then how many modbus to be used
write a c++ code that receives an integer number and display the sum of the number and its revers integer?
How we can determine short circuiting current any plant and for example a plant which power generation is 415 volts and plant load is 500 kw.
what is allowed value of zero sequence impedancce of 6.6 kv nuetral earthing transformer ?what is the actual value
how we can calculate the efficiency of a diesel generator ?
Which motor will you choose which can operate in both lagging as well as leading power factors?
What are the two types of compensation?
Work done in a free expansion process is
What are root loci?
What is the typical enclosure type used for Indoor switchgear / Outdoor switchgear Units? - In Onshore / offshore Units?