Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why Transformers power mentioned in KVA?. and why Generators
and Motors power mentioned in KW?.

Answer Posted / sravani

we can design the transformer for some rated voltage &
rated current ,power factor depends on the load.so,we
cannot predict the p.f. while designing the transformer.
But in the case of generator ,it has to supply real
power (depends on the capacity of the prime mover)& some
amount of reactive power to the system (depends on the
rating of exciter).that's why generators are supplied with
the name plate details including p.f.,kva rating & kw
rating.
in case of motor,it has to take some hp(kw) load
(real power) ,for that it uses some amount of power for
producing the magnetic field (magnetizing power--reactive
power).so,during the design itself we have idea about how
much of load the motor should take (hp load).This is the
reason why the motor is rated in kw,p.f..

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

defination of transistor controlled series capacitor

2677


why cable i burning without tripping. how can protect led street lights

1659


What is the effect on power factor, shown by a trivector meter; incase of reverse phase sequence. If the power factor of a system is lag what meter will show in case of reverse phase sequence connected to the meter. and What in case of lead.

2371


I need a formula to calculate the size of cable as per load but in the terms of length. Please Reply me as i search lot of sites but i did not get the answer.

2135


If two Transformers are connected in parallel having impedance of 50KA in both transformers will the impedance increase or decrease after connecting transformers in parallel?

2140


working principle of oil startar

1956


Pls explan the OLR setting in VCB at HT yard

2734


1.how many types of relays? 2.difference between ATS& STS?

2195


What Normal(Tangent) towers and Tension(Cut-point) Towers?

6285


what is maxemo work permit procedure

2252


while doing high voltage test on 11kv/433 distribution transformer why we only give 28 kv on hv side and 3kv on lv side for power transformers what is the value what factors it depends

2912


Work done in a free expansion process is

1198


What is knee point voltage of transformer?

1203


why the pf of semiconductor device is improved the electrical devices

1886


How to calculate of maximum demand if given 628kw, 785kva, 0.8 p.f.

1694