how does we do bench calibration of a differential
transmitter.
Answer Posted / himanshu amin
dp trasmitter is having range of few w/c. take example of
you want to calibrate 0-50 in h2o dp transmitter. connect
power supply and multimeter to connection point. connect
small hand pump to high side of dp transmitter. keep low
side of dp open to atmosphere. first check 4ma when both
connection are open to atmosphere. then connect hand pump
to high side and give 12.5, 25.0,37.5 & 50 in h20 and check
8,12,16,&20 ma o/p.
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
When doing a liquid seal on a differential flow transmitter , most of the time the sealing liquid will be heavier then the process fluid. For wich application will the sealing liquid be lighter than the process fluid if transmitter is mounted below the process line.
I have a Control VAlve having size of 2 ".Only the known parameter is Pressure drop . Its 2 Kg. Then How to calculate control valve sizing means Cv.
Explain types of valves?
how the arrangement of equipments done in control room
what is installation and commissioning of (fat & sat) of power plant dcs ? this question keeps in desirable conditions of one company .
Explain pH, Conductivity.
Sir, I am working as a Instrument Engineer in Grasim Industries. Can any body provide question answer for interview purpose
What you mean by multi stage control vavles?
Please asked me How calculate DCS controller memory.
Instrumentation Safe Guarding test. How to determine the interval time of the test. eg:Halfyearly,Every year,Every three years etc.
OBJECTIVE TYPE QUESTIONS OF ANALYTICAL INSTRUMENTATION
WHAT ARE THE INSTRUMENTAL DIAGRAMSOF VALVES?
how do we commission inergen system?
Pl send the model question paper of mahagenco account officer post
how to calculate orifice sizing? and tell me if pipe size bet 50mm t0 200mm then we can use pipe flange??? and above 250mm pipe size should i use D & D/2 Flange? is it right or wrong?