Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why the CT ratio secondary is always divided by 5 for eg(
75/5,80/5,50/5)

Answer Posted / vinod g

Purpose of INSTRUMENT TRANSFORMER (CT & PT) is to reduce
the voltage and current respectievly.In EHV/HV/MV voltage
and current for the protection/metering canot be taken
directly as its voltage is very high and required huge
insulation and cost, so PT & CT is using to stepdown
voltage and current. Protection CT and measuring CT are
different class of manufaturing and secondary current
normally one amps but it can be manufactured as per
customer requirement. in 415 V also CT is using if current
is high.

Is This Answer Correct ?    0 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Define pole pitch?

1178


I am designing new project sub station with 220 kV / 11 kV, 40 MVA capacity. This project have many recifier sets, which can generate 3rd harmonics. Now I have to select vector group of This transformer. To minimise 3rd harmonics, what care should I take in selection of Transformer Vecrtor group? If it is Y-Y with open Delta tertiary then what should be the rating & voltage of Tertiary Winding?

1922


Power factor =1.000 at factory in supply. However, PF = 0.8 at motor end. Current = 100 Amp, Voltage = 400 V. What is the power distribution loss? Can I reduce it by adding capacitor at the load feeder?

2112


How to decide CT & PT ratings for a given transmission line carrying some rated voltage?

2378


Please explain me about Relay curves and their sources to read ?

1860


which VFD is better ( LT or HT)

2118


What is the minimum underground tank size capacity considered for firefighting purpose?

2011


how u select control transformer for a mccb panels or any panels?for expample we hav 440 volts maim supply and control volts is 230v?

2242


i m electrical diploma holder i want to do plc $ Scada some body tell me which insitute is best for me near chandigarh

3160


During Testing of Maintenance Free Earthing, How deep should be the Spikes of Earth Test Meter should be inserted in the soil(one spike is 15 Meter & Other spike is 30 Mtrs away from the Main Earth Electrode. Because, recently, we observed that when spike is inserted 3-4 Inch in the earth- results are better, If spike is inserted 1 feet deep than results are increasing.

1990


we use 400/5A ct and 35/roor3KV,/0.1/root3KV,0.1/root3KV pt ratio. What is the multiple factor of this meter.

2067


What is inductance?

1284


Why choke coil is connected in series with starter in tubelight??why starter is connected in parallel to tubelight??

3445


how ct burden,magnetising current,ratio and knee point voltage are related & derived

2252


what is meant by CT`s saturation ? Can we use Metering CT`s with Protetection CT`s ?

2251