why can't we use 5-20mA standard or some other instead of 4-
20mA?
Answer Posted / mohammed abbas
4 - 20 ma is used because one resion is that control system
like DCS AND PLC will accept (1 - 5vdc)only for that resion
by connection 250 ohm resistand accross with ( 4 - 20 ma)
we can get ( 1 to 5 vdc) (1vdc=4ma and 5vdc=20ma) this is
as per ohms law ,V=IR
IF V=4ma*250ohm=1vdc
20ma*250ohm=5vdc
(4 - 20)ma is linear with(0 -100%) and the output will get
linear from 4ma,
| Is This Answer Correct ? | 37 Yes | 2 No |
Post New Answer View All Answers
Can Any body tell me about the Contact or Email id of any good Consultancy which help me to find a job in Instrumentation Field in India .I have Six years of Work Experience in the Same field.Please revert me back on shammi_gwalior@yahoo.com ?
the whole paper was based on Transducers..questions like define repeatability, error,accuracy,precision..den there were many q. on the conversion of Pa to mmHg and other units.. also..der wer few Q. on some level sensors(with diagram)
principle of automatic votage regulator
I need control valve ISA hand book. Is there any site to download that big book containing all the pages. Written by Paul Friedmann
Using your own examples solve a problem involving normal table. (experimental method and analysis)
Why are the uses 24vdc in industries
Why do we have earthing cable in branch cable and shield in the same cable?
please can any one tell me clearly about pid tuning i am confusing about this .how to tune pid easly?
the pump holds on run indication into the dcs and filed local control panel remote push button condition operaton wrong like when the push button pushing conditions the pump is off and the push button release condition the pump is on totally opposite condition . And control room inside give the stop command into dcs just 1secon relay engage and again normal condition. How can I slove
How to Calibrate Radar Level Transmitter in Field
What are the error values can accepted in flow transmitter calibration?could u give any formula for this?
HOW TO SOLVE PROBLEM WITH ENRAF LEVEL TRANSMITTER 854 ATG THAT PASSWARD DO NOT Exist INTO TRANSMITTER TO ADJUST LEVEL WITH PORTABLE PET 847, WRITTEN WRONG PASSWORD , I AM SURE THAT DEFAULT PASSWARD (W2=ENRAF2) IS THIS TRANSMITTER NEED TO REPLACE SOFTWARE AND HOW?
Explain the combusion chamber
Explain types of valves?
For crude application in floating roof tank, how to calibrate a DP Transmitter? How is the floating roof weight considered?