whycircuit breaker is not connected at the generator end
where the capacity of the generator is more say 60MW, 100MW
etc.
Answer Posted / k.prakashchandra
Gen side means usually 11 KV.The generator current at full
load will be very high for 60 MW( 52.5 x MVA A)for an
indoor breaker .Therefore , synchronization and tripping on
fault are done at EHT breaker which is of above 110 KV.For
any fault between the breaker and gen ,the master trip is
employed ,which trips the field breaker ,CB and the governor.
| Is This Answer Correct ? | 13 Yes | 5 No |
Post New Answer View All Answers
Following test should be conducted to find out relative polarity of transformenr terminals A no load test B back to back test C phasing out test D none of above
operation of protection relay watchdog contact?
What is the actual calculation for transformer short circuit test?.
what happen if the load connected to the induction motor is taken away? the same question for synchoronous generator in synch i think that the the exitation voltage will appear on the terminal only if so plz answer me
how to calculate the Neutral transformer impedance?
why we used dc supply for field in dg set
how to enter inverter parameter? without manaual?
if a.c supply is given to the motor,, what happen?
how hydrogen cooled alternator undergo maintanence ? that is hydrogen when come in contact with air can result into explosions .
What is a difference between indoor transformer and outdoor transformer of same rating
what the function breaker failure scheme, how is it operated
What are the effects of adding a zero to a system?
why swityard is necessrry requirement in any bis power distributin systems?
what is the use of piston rings in the engine used for a generator...........
How to reduce -234126219.6403 MVAr generation and by what?