Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why circuit breaker closing time is always higher then
tripping / opening time.

Answer Posted / michael von zechlin

Neither of you are correct and for that matter who really
cares which is greater?
The opening and closing times of circuit breakers are
based on mechanical variables such as charging spring
tension, contact gap, trip mechanism delay etc. The goal
for a circuit breaker is to make or break the contacts as
quickly as possible to either slam the device on line or
open the contacts quickly enough to minimize the time that
an arc exists at the contacts.
What is significant are two measurements that provide an
indication of what the actual operating characteristics of
the circuit breaker are.
First, connect the contacts in series with one another
and a timer such that the circuit goes timer, 1st contact
set, 2nd contact set, 3rd contact set timer. (In one out
the other). Time the opening and closing of the circuit
breaker contacts. This will provide the fastest set of
contact make/break time.
Second, connect the contacts so that they are in
parallel with eachother record the value (This is the
average open/close time).
Once you have done this several times, say about 20,
take an average of each of the first/second measurement
times. Each manufacturer of circuit breakers has published
values for what those readings should be (average.
The significant readings of circuit breaker testing are
not usually related to the timing of the contacts, yes the
contacts can cause a motor to briefly single phase for less
than maybe 2 complete power cycles but not enough to really
matter, the significant measurements are those of mico-ohm
or millivolt drop across the contacts and closing spring
tension.

Is This Answer Correct ?    12 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

wat is the current produced in a 5000v megger? when the positive and negetive terminals are touched on our body get s shock?

1968


List the time domain specifications.

1119


can we install HT panel & LT panel side by side or how much clearance is required ?

1643


PLZ SEND ME SOME UNIQUE PROJECT OF ELECTRICAL ENG (B.TECH)

2012


What should be the length of transmission line so that we can see/obtain the full sine wave of voltage??

1945


How can we find the breaking capacity of a Load breaker switch (LBS) fed from 11 kv supply??ex:50KA, 26kA etc???detailed step vice answer pls.

2075


WHAT KIND OF LIGHTENING PROTECTION SCHEMS CAN BE ADOPTED FOR THE FLAT ROOF OF BIG DIMENSION.

2192


Why we are using only Dyn11 tranformer in distribution system but not using a Dyn1 in distributing system?why not and advantage and disadvantage in both

2793


what is the difference between Power and Distribution transformers ?

2221


how can i change the rotation of the AC single phase induction motor and show me by diagram

1854


what is a bus riser in power system and why it is used

46376


How does a digital electronic meter work??????

2102


what is per unit calculation?looking for simple and strong explanation thk u

2947


which stabilizer is better ? AVR, Servo Stabilizer, Static stabilizer etc & why explain it

2921


why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?

2860