Answer Posted / ranganadh
Long distance communication mA signal is preferable than
mV, V signals to avoid noise. It cann't be predictable with
0 mA, whether the loop was broken or the signal itself. So
to avoid loop break problems we consider 4mA as the lowest
signal. Moreover, it is recommended to put a 250 ohms
resistor at the input terminals of the instrument to get
1VDC for 4mA and 5 VDC for the 20mA and further these
signals will be amplified by instrumentation amplifier in
the instrument circuit.
| Is This Answer Correct ? | 8 Yes | 2 No |
Post New Answer View All Answers
how does we calibrate a square root flow transmitter ,give an example and explain it step by step like range calculation , calibration hook up series connection , zero check , and how to apply pressure , and if not geting proportional output then what should we do ?
Q1]IF THE RANGE FOR FLOW IS -35 TO 125 WHAT WILL BE THE SPAN FOR ABSOLUTE AND FOR NORMAL? Q2]HOW TO CALIBRATE CAPILLARY TYPE LT? Q3]HOW MANY ERROR CALCULATIONS ARE THERE USED IN PROCESS INDUSTRIES? Q4]HOW TO CALIBRATE TEMPERATURE TRANSMITTER? Q5] HOW TO CALIBRATE LEVEL TROLL AND HOW TO CONNECT? Q6]PLEASE TELL ME THE BASIC FOR INSTRUMENTATION WHICH IS APPLIED FOR CALIBRATION AND FOR ALL? PLEASE MAIL THE ANSWER TO honest_yes@yahoo.in
Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell
principle of automatic votage regulator
what is 24vdc live and dry supply
how to connect transmitter measuring sulfur process? 1-by using long impulse line or 2- by using coated short impulse line
Explain why use mmwc unit?
IS there any effect of vortex in low pressure side of the transmiter after the orific in feed water line? if yes then what is the calculation?
what can of fault ofently come in vibration mesurement?
what is the procedure to callibrate temp controller ,pressure controller,etc. suppose a temp controller showing error 1.5 degree centigrate how can i minimize it.
I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?
Can any body help to get Rsemulator 5000 free from internet if possible then give me any link or any help .
how radio frequency level probes works with its controller ? what is its principle ? pls give me brief explanation?
What is ultrasonic flowmeter?
How to Calibrate Radar Level Transmitter in Field