If Two Generators are working parellel in a network and
suddenly the field of one Generator get weakened What will
happened if there is no reverse power relay fixed in that
Generator panel????
Answer Posted / k.prakashchandra
Less excitation?. Then the generator will continue share the
load at leading power factor resulting in higher armature
current as the prime mover is still running and the terminal
voltage of the Gen is reduced.If this current exceeds the
set value ,Gen will trip on OCR which does not allow for
very low pf.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is ignition module of a CAT Gas Genset G-3508 Engine, Alternator SR4B Series. HOw its checked for correct functioning.Is it repiarable or replacable?
how does an centrifugal and screw type chiller will work. which chiller efficiency is high and why.
Explain mechanical rotational system?
WHAT IS VCB SAFETY
block diagram of 2 ups system connected in parallel mode?
given data are load current & power factor cable core size? plz any one update the calculation formula
WHY IL=IPH IN STAR AND WHY IPH=IL/1.732 IN DELTA? WHAT IS REASON BEHIND IT?
what is the common earth
I need to connect a synchronous generator to the grid using automatic synchronization and two circuit breakers (one for synchronization, one for end connection to the grid), how to determinate the required diameter of the cables?
A 2083kva AVR was tested, phase to ground shows continuity, what is the implications
Q.1:What protection will be used on HT and LT side of 33/0.4 KV, MVA transformer. Indicate capacities of protective device to be used. Q.2:Which types of back-up protections are used in the power transformers? What do you understand by the term over travel in the relay? Q.3:How star and delta connected winding transformer are provided from earth fault
what is transient voltage?
what is ground fault in ACB?
What is a Phase shift meter? Where can I get one?
What is transister define the transister ammiter ,base, colector.