Can CT Secondary left open circuited and why(reason)?
Answer Posted / raul
absolutely NOT bcoz during normal operating conditions, the
primary and secondary current are equal and opposite to
each other.........so the mmf of both primary and secondary
are in direct opposition........but secondary current is a
bit lesser than d primary current and this difference is
utilised in magnetising the core.......but if the secondary
is left opened then there will be no demagnetising mmf left
and excessive flux will b generated in the core and due to
this enourmous amount of voltage will b produced in the
secondary which is very harmful for life and CT also. also
there will be a loss of accuracy in future due to residual
flux left in the core.
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
Capacitor is load free component but why ampere meter shows current when capacitor bank breaker close?
Fantio of tranformer
what is a reactive power? what is the relation with power factor?
WHAT IS THE DIFFERENCE BETWEEN GENERAL INVERTER AND SOLOR INVERTER TELL ME PLZ
I would like to know that the fault curretn at base load and at 10% generation will be same? Fault level of BUS remain same with different generation?
sir vizag steel ka junior trainee ka paper kitne number ka ayega
State uses of different types of stsrters with different capacities of motors as below: a. up to 5HP b. above 5hp to 10hp c. above 10hp to 20hp d. above 20hp
HOW DO I CALCULATE THE SETTINGS FOR THE DIFFERENTIAL PROTECTION OF A 12kV/6.6kV, 6MVA,DYN11 XMER WITH PRIMARY SIDE CTR 400/1 AND SEC SIDE CTR 600/1?
hi Is there any possibilities to find out the rotation of a shaft or something else by using electromagnectic waves or by IR rays.If s then can v change the dir., of rotation of the same by remotely?& how? plz dn't any1 say "NO r CAN'T"
If Neutral Grounding Resistor (GR) failed/shorted. Is it repairable.
If we want to change a contactor of faulty one what are the conditions want to fullfil
for what voltage will reactive power be largest in 380 kv line : a) 375kv b)380kv c)385kv
What is the physical significant of power factor?
how to build a network which step down 415v to 1v rms
The specific heats of the gas at constant pressure and constant volume are respectively 1.0 kJ/kg K and 0.72 kJ/kg K; the value of R for the gas is