say a transformer is designed for 33/11kv step down with
ratio 0.33 for load 1 mva. if am giving 11kv as a input
that same transformer what will happen to its o/p voltage.
and whether it can be operated for 500kva
Answer Posted / ankamsreekar
the current rating on 33kv side with full load is 30.30 in
case of 1ph transformer. if we apply 11kv to 33kv side the
transformer rating will be 333.33 KVA insted of 1MVA.the
voltage will be 3.66kv.
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
we are having 15kw and 3kw motor both can run in same time , instead of using copper we are using ug aluminium cable , 35 sq.mm is suitable for its current carrying capacity..?
What are the factors influence the choice of an electrc drive?
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.
Dear sirs, pls check this 4-20ma to RS485 module datasheet,pls guve me some suggestions. http://www.szsunyuan.com/sy/pro_more.asp?Productid=539 Thanks. E-mail:yunianjiang99@gmail.com
what are factors to be consider in electrical installation like load factor,diversity factor .....
what is through fault?
why impudance relay used for medium transmission power system? why not others?
What is the drawback of class b amplifier?
list of tests to be carried out at manufacturers end while purchasing a step up transformer of 11kv to 66kv ,2MVa Capacity.
some time we open engine breaker 8.0 MW load but plant not trip. and another time engine open 4.0 MW load engine trip why? individually engine breaker open & individually emergency stop why difference?
what are types of encoder
define as synchronous generator
How to design the NGR Resistance
what curve and rateing would you use for a three phase 0.75kw motor?
what happen if drive input fail momentry at 48.5 HZ frequency?