We have a 33/11kv switchyard having 12.5 MVA power
transformer. We export & import power through this
transformer. When we export power, the PF will be depend on
GRID PF & when we import power the PF will be depend on our
load PF. but the problem is that,when neither we export nor
import but our 33KV vCB is in close position,our meter read
the power factor 0.14 to 0.25 at that moment. So how can be
we improve the power factor at that moment.
Answer Posted / vinova
try to put some light load on your transformer during this
period if you you wnt to keep the pf high during this
period. it happens because under no load condition the
power fector angle is near 75 and power fector is high. it
happens because tansformer need reactive power for
energising its magnatic circuit. as the outer load is zero
during no load the internal load of transformer is
inductive.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
What are the effects of electrical faults?
How can we calculate the motor frame sizes?
suri transmission
Why sometime AVR and sometime Booster coil is used in Alternator? what is the diferance between AVR & Booster coil due to which they are selected
why we setting 95 deg and 105 deg in wti and oti of distibution transformer ? give the reson for that ?
1. Design a counter which counts 0, 4, 8, 2, 6, and repeats using: 1.a using JK flip flops 1.b using T flip flops 1.c using D flip flops
What is the power requirement of tamil nadu for one month?
How colour picturetube works & how many year it will works.
what you have to see after one week or month from the day of installation of transformer ?
How can you sized or estimate the ligthning arrester current rating?
What are the basic elements used for modeling mechanical translational system?
RATING OF LIGHTENING ARRESTER FOR 11 KV LINE IS 9 KV is ok ,but haw to calculate the KA rating?
Why efficiency in thermal power plant is low?
How many types oil using in transformer ? How many letars using in transformer..?
what is ic 01,ic 06 ?is it types of cooling?