Answer Posted / singa
CTs are having both measuring as well as protection cores.
Measuring cores:
In a HT lne, current value is in terms of few hundrest to
kilo amps. In practical these cannot be measured by meters
direclty. Hence the current in the transmission line will
be stepped down to the standard values for example 2000/1A.
THis refers to the flow of 1A at CT secondary when 2000A
flows in HT line.
Protection core: As the fault current is very high during
the time of fault, this increase in current is used to trip
the faulty section. In order to sense the fault current,
protection cores of CTs are used to feed the protection
relay.
Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
how we start 40w tube light with 4 diodes,2capacitors,1 choke and without starter.(a product avilable in market which lights burnt tube lights also)
for a 500 KVA connected load, I calculated 30% of capactor for power correction. Even after using 225 KVR capactor PF is not improving. What could be reason for low Phase correction factor?
Is it possible to download the Siemens Selection Chart(TYPE 2 coordination) for 1) fuseless selection 2)Fuse selection
How to Make relay co ordination chart for a Electrical power distribution of a plant
what is the best method of grounding in 30 MW generator?
An automatic water heater is an example of which type of control system?
what is mean by ideal infinite bus? why it is required to consider in fault short circuit calculations?
how to commissioning the genset with amf panel?
IF alternator SCR value will be high means what happen in alternator efficency at operating power factor of 0.8
raleigh method
If you don’t have coal, salt and copper, then how would you earth your connection temporarily at a camp site.?
Why we are going for converter transformers for DC drives application instead of distribution transformer?
in dc suppy frequency is zero why? if dc frequency is zero how to exist dc transients and ac transients
We are planning to synchronized DG's with our captive plant in the event of black start of plant, but before sync we checked voltage of DG with our plant voltage and it varies from 5 V to 450 V. So in this condition how we can sync DG with plant ?
How i can decide that HVDC line is best for transmission.