Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have carried out wiring for lighting in a shed in
Industrial area which contains Metal halide lamps & have
balanced in 3ph.Now when we put all the lines on in the
daytime the current taken at 3phases at MCB comes to be
equal i.e.28,29,28Amps respectively but in the night time
i.e between 7p.m.to 11p.m. at the same MCb the current is
52,59,62Amp, though I have fit 63A MCB it is tripping in
the above period.What may be the reason.?
Note: This industry is located in industrial area where
majority of steel ingot manufacturing plants are there.
Whether this may be due to harmonic? what should I do to
overcome above problem.pl suggest urgently.

Answer Posted / h r jadhav

pl check the maloperation of mcb or correct rating of mcb/
secondly the power factor may be very low of the metal hal
lamps during day time that may be compenseted by bus
capacitors and which are disconnected at the time of no
work. there by increasing current and mcb get tripped/ pl
use energy efficient electronics ballast.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Determine a suitable number of slors and conductors per slot for the starter 1 winding of a 3 phase, 3300 V. SO Hz 300 rpm alternator. The diameter is 2.3 m

2836


This is reqd for a 1MW Solar power plant..We have 2DC outputs from the solar panels Connected to 2INVERTOR panels.. Output from invertor is 3ph,280v,500kva,50hz.These are connected to individual ACB.This has to be stepped up to 11KV ,1250KVA SYSTEM.Now can I use (1) one more ACBTO GIVE A COMBINED OUTPUT OF 1000KVA,280V & STEP UP THE OUTPUT BY USING a single two winding 3 ph transformer 11kv/1250kva. or (2)use the two outputs and connect to one three winding transformer of above rating..Pls suggestwith details.

2479


What is the estimated total hydropower potential of india?

1138


What is an alternator impedance value?

2859


Describe Non I.S. Earth System and why is it used?

1789


Define early construction of human being

1913


how can found motors folt current ? how can disided circuit breakers caoicity and breaking capicity ?

2172


what is the effect of earth on capacitance in 3-phase and 1- phase transmission line?

2367


what is laser diodes?

1160


When we use air circuit breaker, it has O/L protection ,time delay SC protection, Instataneous SC protection & ground fault protection. They all have some setting range. But what is the suitable/allowable setting for the above protection which will be safe for the equipment? For example-O/L protection setting have a range of (0.4,0.45,0.5,0.55,0.6,0.65,0.7,0.8,0.9,1.0)xIn Time delay SC protection have a range of (1.25,1.5,2,3,4,6,8,10,12)xIn Time delay setting is 0.02,0.1,0.2,0.3,0.4 Instataneous setting is fixed to 20xIn Gound fault setting is given 100A,300A,600A,900A,1200A This setting are for 2500A ACB. So what will be the basic allowable setting for the above protection? is there any formulae to calculate this<

2156


sir i am apearing for nic exam.i dont know exam pattern.can you please send me some model papers

1989


how we provide neutral earth on synchronising panel as per electrical standards?

2101


What is the difference in calculating size of AC cables compared to calculating size of DC Cables? Usually DC Cables are larger than AC Cables although they have the same ampacity. Why is it?

1987


What is highest size of HT motor like 11 kv or 33 kv,and how to make it 750 rpm.i think the size will be very big.any idea ? pl. reply..

1933


why they were using TRIAC instead relay in some controllers and what is the advantages.

2029