what happens if we are having very very high cavity and
flashing in a control valve..??? is it stops
working...immediately... or eroded...slowly

Answer Posted / www.islamqa.com

Actually the valve will not stop working, but as a result
of continous errosion it will be useless and you will need
to change the valve completely.

talking about solution need more details about the
situation but here is the basic guide lines:

# To avoid flashing:
====================

1 - valve selection with high Fl.
Fl:valve pressure recovery coefficient, and this introduced
by MASONILIAN as: Fl=(P1-P2/P1-Pvc)^.5 - and Fl max is 1.

where FISHER introduced Km =(P1-P2/P1-Pv) - and this is a
valve parameter presented by vendor and it's calculated by
lab tests, and usin Km we can get allowable(P1-P2) which
will not cause flashing.

2 - using anti cavitation trim, which generate multi vena
contracta points in the presuure profile, and this prevent
pressure drop below Pv.

3 - To cool down the process material to make Pv very low.

4 - To change the valve position to another place with high
pressure, to make pressure drop through the valve away from
PV.


And anyway if there is no escape from flashing, it's better
to sustain flashing within the valve to assure that we will
not have a cavitation when pressure recover, and liquid can
be recovered and bubbles can implode any other place away
from the valve.

and this can be achieved by heating up the process liquid
so we raise Pv, and a good indication for us to be sure
that flash will be sustained is p2, as we can know P2 at
downstream pipeline and make sure that it's below Pvc of
the process liquid.

Regards,

Ahmed Sabry
Control and Instrumentation Engineer
GPC - General Petroleum Company
ahmedsabry.online@gmail.com
CELL.: 00 2 0121367310

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

all questions related to instrument technician in any offshore oil and gas company.

21172


sir,would you please send me the Hindustan petroleum corporation limited papers(HPCL).my e-mail ID is ujjwal_sharma1983@yahoo.com

1893


What denotes the 5/8mm in the 3300XL 5/8mm proximitor probe?

1068


i want to find out iffco get test paper

12423


How can measure flow in oil line?which type of transmitter is generally used?

3700






Why even multiple power supplu r used in instrumentation system?

4310


full process of gas turbin?

1657


How INtools is useful for routine Instrument maintenance?

1669


Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...

1947


Which type of diaphragm use in costic line, dm water line, natural gas line, oil line?

808


What is difference of fanuc alpha series 16i and 18i controller.also what is differnce betn TC and MC controller

1973


diff between neutral ,ground,phase , earthing and shielding?

1953


Can combine control system for Emergency control system (ESD)and Fire & Gas System ( F & G) is possble to built and offer to client? Can such system is as per Norms in India?

1647


Why mmwc unit is used?

856


Reason for capillary type dp level transmitter fluctuation

1615