To test Transformer we give HT side 440V to see wheather
that it is producing 17.6V on LT to verify Voltage ratio is
correct or not but when we give the 440V voltage to LT side
then what will happen to HT voltage ?
Answer Posted / nithi
For ratio-test,the second answer may be correct.
But at the same time,if we apply high voltage in LV
side (in ratio-test also)for a longer period (in seconds),
LV winding cannot withstand, result in insulation break-
down,blown-out of fuses.
generally ratio-test is conducted with the
specified (allowable) voltage magnitude.so,practically this
much of voltage is not applied for LV side.I hope,this
answer will be correct.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Define bibo stability.
how withstand of hi-pot test outputs of transformer wire 2.5mm
what is The difference between national electrical code and I.S.Code (electrical) and what is the value of NEC in electrical engineering field
what is the solution for meger test failed the MV cable?
What happened if C.T mount at any cable or Bus bar in wrong direction . C.T going on proper work or not . C,T direction is essential thing to properly work.
what is differant beetween overload current and phase current?
what is the difference between earthing and unearth
AL=0B9H,bl=75H, ADD AL,BL AL=____________? CF________? OF___________?
How many Zones can be in Conventional type fire alarm system & how can we detect the fire in Conv. type FAS?
I want to merge a cable..in between two metering Cubicals which contains CT's and PT's and Energy meter..before taking merger..what are the common things required?
Is it acceptable of installing an earth pit in planters area where bare copper cable, earth rod and connection are susceptible to corrosion due to water?
why most of junction box vendors providing T5/T6 Temp class jb's for T3 area any special reason?
how to calculate singlephase motor efficiency?
why steady state stability limit is greater than transient stability limit ? How it can be explained ?
what will happen if synchronous machine rotor fed from single phase ac supply