Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

To test Transformer we give HT side 440V to see wheather
that it is producing 17.6V on LT to verify Voltage ratio is
correct or not but when we give the 440V voltage to LT side
then what will happen to HT voltage ?

Answer Posted / manohar mishra

For ratio test, only the change in voltage is to be measureD. If 440 V is fed to LV, HV voltage will go to a HIGH VALUE (11kV) making it difficult to measure. Blowing of fuses do not occur as there is no flow of current.

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I NEED RRB SYLABUS FOR JE ELECTRICAL ,PLEASE SEND TO MY E- MAIL ID joo28_eee@yahoo.co.in

2907


A cotter joint is generally used to transmit

1308


why ht cable end termination don't have a gland?

2994


design of IGBT firing circuit for 11KV

2713


v/f drive basic princeple

2542


how to find impedance , mutual indatnce in transmission lines

2378


will 1050kva DG set withstand for back charge of 16MVA transformer

1912


What is the two pole structure?

2009


What is industrial plc

1908


11KV AND 22KV NETWORK KW CAPACITY IN RING AND RADIAL?

2056


we have consol make 3 phase servo stabilizer for cnc m/c. while installing the earth neutral voltage is 1.7 volts at stbilizer off condition and when stabilizer get on en voltage reaches 4.8 volts (new earthing is done and neutral is helthy condition all phase to neutral volts 440,442,441 v)why this happen.solution for cause.

7228


I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

2022


distribution is maximum done by a)radial b)network c) parallel d)b & c

2000


electrical knowelge

1235


orifice sizing how done, checking & selection

2021